Application
Switchgear Current Transformers (SCTs) can be used for measuring, revenue metering and protection applications inside of both switchgear and medium voltage breaker apparatus. Peak Demand SCTs are designed and manufactured in accordance with customer specifications and industry standards. The Peak Demand SCT-650D has a larger core to allow for larger relay burdens up to C400.
Construction
The core is constructed from wound layers of electrical grade steel. The core is wrapped with insulation to protect the windings from damage. Cores are wound with enamel coated copper wire to ensure against potential short circuits. The core and coil assembly is insulated with a polycarbonate plastic case to provide for long life in indoor environments. Secondary terminals are brass #10-32 screws with a flat washer, lock washer and regular nut.
Technical Specifications
Compatible Medium Voltage Breakers
All Eaton VCP Styles; GE Power/Vac; Square D Type FG-2
Cross Reference
GE ITI 785, 786; GE JAG-0; ABB SCV-D; Amran CT103, CT104
Test Reports
Each SCT has a unique serial number which allows the customer to track each test record. Certified test reports and curves are stored electronically and provided with every shipment.
UL
UL File #E492538